1. General Introduction
YTA70P temperature transmitter owns almost complete same specifiation as YTA70, unique compact rail mount details which enable to be mounted in a cubic panels, saving mounting spaces.
2. Sensors inputs, measure range and accuracy
Sensor Type
|
Standard
|
Measure range
|
Minimum Span
|
Accuracy
|
Temperature effects/10℃
|
℃
|
℉
|
℃
|
℉
|
T/C
|
B
|
IEC60584
|
-400 to 1820
|
752 to 3308
|
200
|
360
|
±0.1% or ±1℃
|
±0.05% or ±1℃
|
E
|
-100 to 1000
|
-148 to 1832
|
50
|
90
|
±0.1% or ±0.5℃
|
±0.05% or ±0.25℃
|
J
|
-100 to 1200
|
-148 to 2192
|
50
|
90
|
K
|
-180 to 1372
|
-292 to 2502
|
50
|
90
|
N
|
-180 to 1300
|
-292 to 2372
|
100
|
180
|
R
|
-50 to 1760
|
-58 to 3200
|
200
|
360
|
±0.1% or ±1℃
|
±0.05% or ±1℃
|
S
|
-50 to 1760
|
-58 to 3200
|
200
|
360
|
T
|
-200 to 400
|
-328 to 752
|
50
|
90
|
±0.1% or ±0.5℃
|
±0.05% or ±0.25℃
|
L
|
DIN43710
|
-100 to 900
|
-148 to 1652
|
50
|
90
|
U
|
-200 to 600
|
-328 to 1112
|
75
|
135
|
Lr
|
Gost 3044-84
|
-200 to 800
|
-328 to 1472
|
50
|
90
|
±0.1% or ±1℃
|
±0.05% or ±1℃
|
W3
|
ASTM E988-90
|
0 to 2300
|
32 to 4172
|
200
|
360
|
W5
|
0 to 2300
|
32 to 4172
|
200
|
360
|
RTD
|
PT100
|
IEC60751
|
-200 to 850
|
-328 to 1562
|
10
|
18
|
±0.1% or ±0.1℃
|
±0.05% or ±0.05℃
|
Ni100
|
DIN43760
|
-60 to 250
|
-76 to 482
|
10
|
18
|
±0.1% or ±0.2℃
|
±0.05% or ±0.05℃
|
mV
|
—
|
-800 to 800 mV
|
±2.5 mV
|
±0.1% or ±0.01mV
|
±0.05% or ±0.05mV
|
ohm
|
—
|
0 to 7000 Ω
|
±25 Ω
|
±0.1% or ±0.1Ω
|
±0.05% or ±0.05Ω
|
3. Model and suffix codes
Main Code
|
Suffix Codes
|
Description
|
YTA70P
|
|
|
|
Temperature Transmitter (Panel Mount Type)
|
Output Signal
|
-J
|
|
|
4 to 20mA DC with digital communication (HART 5/HART 7 protocol)
|
—
|
|
A
|
|
Always A
|
Optional codes
|
|
|
/V2S
|
ATEX, FM, IECEx, and CSA Intrinsically safe Approval
|